MKH6500-42
6500W Hybrid solar inverter with charger
This product manual provides important recommendations related to the Magic-Kepler integrated
inverter-controller, including installation, operation, precautions, and more. Please read this
manual carefully before using the product
- PV, utility mains, and the battery can power the load simultaneously.
- After configuring the WiFi module, operating parameters can be monitored remotely(This feature is not
- applicable to MK1200-12).
- Primary and secondary AC outputs, allowing differentiation based on the importance of the electrical loads
- (Only the MKH6500-42 has a second output, while other models only have one AC inverter output).
- Equipped with CAN/RS485 for BMS communication, facilitating storage battery management(The MK1200-12
- does not have BMS function).
- High-frequency inverter: compact size, lightweight.
- Pure sine wave AC output,With power savina mode function, reduce no-load loss
| 1.Utility power parameters | ||||
| Item | Mode | MKH5000-22 | MKH6500-42 Series | Note |
| Input Voltage | Main Input | L+N+PE | ||
| Input Voltage | 230Vac | Adjustable208/220/ 230/240Vac | ||
| Input Voltage Range | 90~280Vac(Adjustable) | |||
| Input Low Loss | 154Vac(Default)Adjustable:90~154Vac | APP/GEN mode | ||
| 185Vac(Default)Adjustable:170~200Vac | UPS mode | |||
| Input Low Recovery | Low Loss Voltage+9V | |||
| Input High Loss | 264Vac(Default)Adjustable:264~280Vac | APP/GEN mode | ||
| 264Vac | UPS mode | |||
| Input High Recovery | High Loss Voltage-9V | |||
| Input Frequency | Rated Frequency | 50/60Hz | ||
| Frequency Low Loss/Recovery |
40/43.5Hz@50Hz(UPS mode) 50/53.5Hz@60Hz(UPS mode) 40/43.5Hz@60Hz(APP/GEN mode) |
|||
| Frequency High Loss/Recovery |
60/56.5Hz@50Hz(UPS mode) 70/66.5Hz@60Hz(UPS mode) 70/69.5Hz@60Hz(APP/GEN mode) |
|||
| Input Current | Rated Current | 21.7A | 26A |
Vrms=230V Line mode at 100% capacity. Excluding the charger. |
| Max. Current | 40A | Bypass Current | ||
| Note:When the external circuit breaker specification exceeds 40A,the maximum input current is 40A. When the external circuit breaker specification is less than 40A,the maximum input current depends on the external circuit breaker specification. | ||||
| 2.Battery parameters | ||||
| Item | Mode | MKH5000-22 | MKH6500-42 Series | Note |
| Battery Information | Number of Batteries | 2Pcs | 4Pcs | 12V/Pcs |
| Automatic Start Function | Yes | |||
| Battery Test Function | No | |||
| Battery Type | AGM/FLD/LIB/FEL/CUS | |||
| Rated Battery Voltage | N*12V | @25℃ | ||
| Battery Management | Yes | |||
| Battery Protection | Battery Overvoltage | 30.5V | 61V | |
| Battery Undervoltage | 10.5V*N | Adjustable:10*N~11*N | ||
| Battery Low Voltage Alarm | 10.8V*N | Adjustable:10.3*N~11.3*N | ||
| Overcurrent Protection | Fuse | Fast Acting | ||
| Note:N = Number of batteries. | ||||
| 3.Charging parameters | ||||
| Item | Mode | MKH5000-22 | MKH6500-42 Series | Note |
| Charging(Utility Mode) | Charging Voltage | FV mode:27V CV mode:28.2V | FV mode:54V Adjustable: 53.2~55.6V CV mode:56.4V Adjustable: 56~58V | |
| Temperature Compensation | No | |||
| Charging Current | 2~160A | 2~120A | Adjustable | |
| Default Charging Current | 80A | 60A | ||
| Charging Method | Two/Three/Auto Adjustable | Three states:CC/CV/Float Two states:CC/Float | ||
| Charging Voltage Accuracy | ±5% | Calibrated via RS232 | ||
| Charging(PV Mode) | PV Charging Method | MPPT | ||
| Max.PV Input Power | 27A/9000W | |||
| Efficiency | 99.5%(Max.) | |||
| MPPT | 60~450Vdc | |||
| Min. PV Voltage | 80V | |||
| Max. PV Voltage | 500Vdc | |||
| Max. PV Charging Current | 160A | 120A | ||
| MAX.Charging Current | / | 160A(Max. allowable value)Default:120A | 120A(Max. allowable value)Default:100A | Adjustable |
| 4.Output parameters | ||||
| Item | Mode | MKH5000-22 | MKH6500-42 Series | Note |
| Output Power Rating | Output | L1+N1+L2+N2+PE | ||
| Max. Output Power | 5000W | 6500W | Power reduction when powered by battery only. | |
| Output Voltage | Rated Voltage | 230Vac | Adjustable:208/220/230/240Vac,Manually set via RS232 or LCD. | |
| Waveform | Sine Wave | |||
| Voltage Regulation | ±5% | |||
| DC Offset | ±100mV(Battery mode) | No-load and Linear load mode | ||
| Output Frequency | Rated Frequency | 50/60Hz | 50/60Hz Auto-Select(Default On) | |
| Battery Mode | 50/60Hz | |||
| Frequency Regulation | 0.10% | |||
| Utility Mode |
50Hz: (40~60)Hz (UPS mode) (40~70)Hz (APP/GEN mode) 60Hz: (50~70)Hz (UPS mode) (40~70)Hz (APP/GEN mode) |
50Hz: (43.5~56.5)Hz (UPS mode) (40~70)Hz (APP/GEN mode) 60Hz: (53.5~66.5)Hz (UPS mode) (40~70)Hz (APP/GEN mode) |
||
| Overload Capacity | 1 minute@102%~120% load,10 seconds>120% load.(Battery mode) | |||
| Output Short Circuit protection | Battery Mode | Current Limiting | ||
| Utility Mode | Circuit Breaker (40A) | |||
| 5.Transfer time parameters | ||||
| Item | Mode | Parameters | Note | |
| Transfer Time | Utility Mode to Battery Mode | 10ms(Typical Value) | UPS mode | |
| 10ms(Typical Value) | Appliance (APP) Mode | |||
| 20ms(Typical Value) | Generator (GEN) Mode | |||
| 6.Efficiency parameters | ||||
| Item | Mode | MKH5000-22 | MKH6500-42 Series | Note |
| Efficiency | Utility Mode | >99.5%@6KVA |
Full R Load: Efficiency vs. Load Curve at Different Input Voltages; No Battery Connection Required. |
|
| Battery Mode | 93.5%(Max) | 94%(Max) | Full R Load: Efficiency vs. Load Curve at Different Input Voltages. | |
| Standby Power | <35W | <30W | No Load / Battery Mode | |
Application scenariosMORE >